Features
- Isolated Transformer: All Titanium Series UPS units include an internal isolation transformer. This rugged design ensured low common mode noise and low normal mode noise.
- In-rush Capabilities: The Titanium Series UPS systems include a high in-rush capability. Supporting an overload for 150% will allow the user to properly size their UPS.
- Customized Back Panels: Back panels are customized per customer. Allows for specific designs to ensure all power requirements are supported.
- External Maintenance Bypass Systems: External Maintenance Bypass Systems are available in two types – isolated and non-isolated version. Consult factory for recommendations .
Downloadable Product Specs
Specifications
| MODEL | TITANIUM SERIES UPS | ||||
|---|---|---|---|---|---|
| 5.2kVA (H) | 6kVA (H) | 8kVA (H) | 10kVA (H) | ||
| Capacity | 5.2kVA / 5.2kW | 6kVA / 6kW | 8kVA / 8kW | 10kVA / 10kW | |
| INPUT | |||||
| Input Voltage (range) | 208/220/230/240VAC / +28%/ -15% @ full load | ||||
| Phase | 1 Phase with neutral | ||||
| Frequency Range | 46Hz ~ 54Hz @ 50Hz System, 56Hz ~ 64Hz @ 60Hz System | ||||
| Power Factor | ≧ 0.99 at 100% Load | ||||
| OUTPUT | |||||
| Output Voltage | 104/110/115/120/208/220/230/240 | ||||
| Phase | 1 Phase with neutral | ||||
| Frequency Sync Range | 46Hz ~ 54Hz @ 50Hz System, 56Hz ~ 64Hz @ 60Hz System, (Batt Mode) +/- 0.1% Hz | ||||
| Output THD | ≦ 2% at 100% Linear Load / ≦ 4% at 100% Non-linear Load (PF≥0.8) | ||||
| Voltage Regulation | ± 1% | ||||
| Overload – AC Mode | 100%~110% for 1hr / 110-130% for 1min / >130%: 1sec | ||||
| Overload – Battery Mode | 100-110%: 30sec / 110-130%: 10sec / >130%: 1sec | ||||
| Current Crest Ratio | 3:1 Max | ||||
| EFFICIENCY | |||||
| AC Mode | 90% | ||||
| Battery Mode | 88% | ||||
| ECO Mode | 97% | ||||
| BATTERY | |||||
| Battery Voltage | 240, Nominal, 270 Float | ||||
| Battery Backup Time | 8min | 7min | 4min | 2min | |
| Recharge Time | 7 hours at 90% | ||||
| Quantity | 20 | ||||
| Internal Batteries | 20 x 9AH | 20 x 9AH | 20 x 9AH | 20 x 9AH | |
| PHYSICAL | |||||
| Dimensions WxDxH | 9.8″W x 28.2″D x 32.5″H | ||||
| Weight (lbs) | 266 | 266 | 301 | 301 | |
| ENVIRONMENT | |||||
| Operating Temperature | 0-40°C (the battery life will decrease when > 25°C) | ||||
| Operating Humidity | <95% non-condensing | ||||
| Operating Altitude ft (m) | 2,000ft | ||||
| Heat Dissipation (BTU/Hr) | 1970 | 2530 | 3372 | 4215 | |
| Acoustic Noise Level | 55-60dB at 1 meter | 60dB at 1 meter | |||
| COMMUNICATION | |||||
| RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC | ||||
| MODBUS Card | Power Management with MODBUS communication | ||||
| Optional SNMP | Power management from SNMP manager and web browser | ||||
| AGENCY APPROVAL | |||||
| Safety | UL 1778 / IEC 62040-2:2018 | ||||